GDT
Home > Products > GDT >

2-electrode tubes/Y49 type

Conforming standards:
●RoHS compliant

Product Details

Specification Parameters

Attachment Download

Features:

●Large capacity arrester with maximum discharge current of 100kA

●Best suited for lightning surge countermeasures for railway signal,electrical power transmission and other large capacity lines


External view:

QLKBXTCSM)@IFJL([96~520

Item

Conditions

Performance

Y49-230

Y49-350

Y49-450

Y49-550

Y49-700

Y49-930

Y49-1000

Y49-1200

Y49-1400

Y49-12kV

DC sparkover voltage

100V/s

230V±20%

350V±20%

450V±90V

550V±100V

—

500V/s

—

700V±100V

930V±90V

1000V±150V

1200V±200V

1400V±150V

—

5Kv/s

—

12kV±3kV

Impulse sparkover

voltage

10/200μs·3kV

≦1000V

≦1500V

—

≦2800V

—

Insulation

resistance

DC100V

≧10,000MΩ

—

DC250V

—

≧10,000MΩ

≧100MΩ

—

≧100MΩ

—

DC500V

—

≧10,000MΩ

——

≧10,000MΩ

——

DC1000V

—

≧100MΩ

Electrostatic capacity

1MHz

≦10pF

—

≦10pF

—

AC discharge

current

AC15A﹒80s

30 times

—

AC1000A﹒0.3s

—

30 times

—

10 times

—

AC20A﹒80s

—

30 times

—

AC70A﹒20s

—

20 times

—

20 times

—

AC500A﹒0.3s

—

10 times

—

10 times

—

Impulse

discharge

current

8/20μs﹒20kA

30 times

—

10/200μs﹒20kA

—

30 times

—

8/20μs﹒40kA

—

5 times